LST 45681-300 Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
45681-290_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Description
The Integrated Base Sounders 45681-277, 45681-290
and 45681-300 are fi tted into a round, white plastic
case with an integrated base for accommodating au-
tomatic Fire Detectors or Strobes Series XP95 or Dis-
covery.
The sounders are powered and actuated as modules via
the ADM loop with Apollo/Discovery protocol. They can
be used in combination with a detector or strobe, or as
stand-alone device. For the latter case an optional white
or red plastic lid is available. Furthermore, the sounders
are equipped with an integrated dual-isolator module.
Two different tone types, depending on the sounder
model, are available, and they can be selected during
parameterisation of the Fire Detection Control Panel Se-
ries BC216. If several sounders are actuated in parallel,
they are synchronized by Fire Detection Control Panels
Series BC216 to generate a uniform warning tone.
In case of activation, the sounder is tested acoustically
by means of an integrated microphone.
The address of the sounder as well as the sound level
are selected by means of a DIL switch.
The base sounders have been designed for indoor
mounting. An optional mounting plate is available for
surface mounted cabling.
ADM loop technology with
Apollo/Discovery protocol
Integrated detector base with
dual-isolator
Warning tone 1kHz
Slow whoop tone – NEN 2575
Emergency signal tone – DIN 33404
Sound level selectable in two steps–
up to 91dB(A)
Integrated acoustical self test
Integrated Base Sounder
45681-277, 45681-290, 45681-300
Specifi cations
Operating voltage 17 – 28VDC
Current consumption max. 200µA (sounder off)
max. 5mA (sounder on)
Sound level 55 – 75dB(A) or
75 – 91dB(A)
Ambient temperature -20°C to +60°C
Dimensions ø × H 115 × 38 (mm)
Colour white
Weight 140g