Klaxon 105 DC Smoke Alarm User Manual


 
EN54-3
Fire Alarm Device Sounder
Type B: For indoor or outdoor use
18-980542/543/544/653/655/588/620/621/658/659/657
Technical Data: Document 18-186528
0832
07
0832-CPD-0615 (Sounder-LED Beacon)
0832-CPD-0616 (Sounder-Xenon Beacon)
0832-CPD-0617 (Sounder)
Nexus 105 DC Sounder & Sounder-Beacon
Installation Instructions
EN
Klaxon Signals Ltd, Oldham, OL4 1HW, UK
Phone +44 161 287 5555 Fax +44 161 287 5511
E-mail sales@klaxonsignals.com
Issue 7 (January 2008) 18-186456
Copyright © Klaxon Signals Ltd
www.klaxonsignals.com
T
one Tone Type Tone Description / Application Dip Switch 3rd Stage Peak Sound Sounder
(
S1/S2) Tone Level (dBA@1m) Current (mA Avg)
1. 970Hz (BS5839-1:2002) O-O-O-O-O-O 18 105 31
2
. 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O-O-O-O-I 1 105 28
3
. 800Hz – 970Hz @ 1Hz (BS5839-1:2002) O-O-O-O-I-O 1 104 25
4
. 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) O-O-O-O-I-I 1 105 17
5
. 970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002) O-O-O-I-O-O 1 105 27
6
. 554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 ) O-O-O-I-O-I 1 103 20
7. 500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) O-O-O-I-I-O 1 108 19
8. 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) O-O-O-I-I-I 1 102 10
9. 500 – 1200Hz,0.5s/ 0.5s OFFx 3/1.5s OFF(Australia AS1670 Evacuation tone) O-O-I-O-O-O 1 106 13
10. 550Hz/440Hz @ 0.5Hz O-O-I-O-O-I 19 104 21
1
1. 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone) O-O-I-O-I-O 1 105 13
1
2. 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone) O-O-I-O-I-I 1 107 16
1
3. 1200Hz – 500Hz @ 1Hz (DIN 33 404) O-O-I-I-O-O 1 109 22
1
4. 400Hz O-O-I-I-O-I 18 101 16
1
5. 550Hz, 0.7s/1000Hz, 0.33s O-O-I-I-I-O 1 105 25
16. 1500Hz – 2700Hz @ 3Hz (Vandal Alarm) O- O-I -I -I -I 1 113 32
17. Simulated Bell O-I-O-O-O-O 1 107 18
18. 840Hz O-I-O-O-O-I 1 110 26
19. 660Hz O-I-O-O-I-O 10 102 25
2
0. 660Hz 1.8s ON/1.8s OFF O-I-O-O-I-I 19 102 14
2
1. 660Hz 0.15s ON/0.15s OFF O-I-O-I-O-O 19 102 14
2
2. 510Hz, 0.25s/ 610Hz, 0.25s O-I-O-I-O-I 1 103 24
2
3. 800/1000Hz 0.5s each (1Hz) O-I-O-I-I-O 1 106 25
24. 250Hz – 1200Hz @ 12Hz O- I-O -I -I -I 1 101 23
25. 500Hz – 1200Hz @ 0.33Hz. O-I-I-O-O-O 1 108 21
2
6. 2400Hz – 2900Hz @ 9Hz O-I-I-O-O-I 1 113 39
27. 2400Hz – 2900Hz @ 3Hz O-I-I-O-I-O 1 111 39
28. 800Hz – 970Hz @ 100Hz O- I-I -O -I -I 1 104 23
2
9. 800Hz – 970Hz @ 9Hz O-I-I-I-O-O 1 104 27
30. 800Hz – 970Hz @ 3Hz O- I-I -I -O -I 1 105 28
31. 800Hz, 0.25s ON/1s OFF O- I-I -I -I -O 1 103 8
32. 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220) O - I - I - I - I - I 1 108 20
33. 340Hz I-O-O-O-O-O 1 101 17
34. 1000Hz I-O-O-O-O-I 18 106 25
35. 1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265) I-O-O-O-I-O 1 104 34
36. 660Hz 6.5s ON/13s OFF I-O-O-O-I-I 19 102 9
37. 1000Hz/2000Hz, 1s each I-O-O-I-O-O 1 108 25
38. 720Hz, 0.7s ON/0.3s OFF I-O-O-I-O-I 1 104 16
39. 970Hz, 0.25s ON/OFF I-O-O-I-I-O 1 105 17
40. 2800Hz, 1s ON/OFF I- O-O -I -I -I 1 106 20
41. 2800Hz 0.25s ON/OFF I-O-I-O-O-O 1 106 19
42. 2400/2900 @ 2Hz I-O-I-O-O-I 1 113 38
43. Chime, 554Hz/440Hz Single shot ‘ding dong’ I-O-I-O-I-O1 100 15
44. Chime, 554Hz/440Hz Repeating ‘ding dong’ I- O-I -O- I- I 1 102 15
45. Chime, 970Hz/800Hz Single shot ‘ding dong’ I-O-I-I-O-O 1 101 36
46. Chime, 970Hz/800Hz Repeating ‘ding dong’ I- O-I -I- O- I1 100 36
47. Hooter, Repeating I- O-I -I -I -O 1 102 13
48. Gentle alarm - Tone 2, rises slowly to full volume over 30s I - O - I - I - I - I 1 105 28
49. Time-Out Alarm – As Tone 2, cuts off after 10 mins I-I-O-O-O-O 1 105 28
50. Time-Out Alarm – As Tone 2, cuts off after 2 mins I-I-O-O-O-I 1 105 28
51. 750Hz 0.33s ON/0.51s OFF I-I-O-O-I-O 1 103 8
52. 750Hz 0.51s ON/0.33s OFF I- I-O -O -I -I 1 103 15
53. 550Hz, 0.33s/1000Hz, 0.7s I-I-O-I-O-O 1 106 25
54. 600Hz – 900Hz/ 0.9s I- I-O -I -O -I 1 104 31
55. 660Hz – 680Hz/ 0.9s I- I-O -I -I -O 1 101 28
56. 670Hz – 725Hz/ 0.9s I - I - O - I - I - I 1 104 25
57. 920Hz – 750Hz/ 0.9s I-I-I-O-O-O 1 104 30
58. 700Hz - 900Hz, 0.3s/0.6s OFF I- I-I -O -O -I 1 104 11
59. 900Hz - 760Hz, 0.6s/0.3s OFF I- I-I -O -I -O 1 105 19
60. 750Hz I - I - I - O - I - I 18 103 22
61. Power Only– Use with Stage 3 control for manual/intermittent chime triggering I- I-I -I -O -O 43
62. Power Only– Use with Stage 3 control for manual/intermittent chime triggering I - I - I - I - O - I 43
63. Power Only – Use with Stage 3 control for manual/intermittent horn triggering I - I - I - I - I - O 47
64. Reserved for future use I - I - I - I - I - I
DE
FR
NL ES